Structural Notes For Civil Engineers

  

BEST CIVIL STRUCTURAL ENGINEERING NOTES

 Materials

1: Concrete of min. 28 days cylinder crushing strength of 3000 psi (Shall confirm to the relevant item in specifications provided with these drawings) Shall be used in construction of all the structural members including foundation Footing, foundation beams, floor slabs, beams, columns, stairs, slab etc.

2:Reinforcing bars used in structural members shall be of min. Yield strength of 40,000 psi Confirming to astm a-615.

 

Standard bar cut off points:

1:Standard bar cut off point for the negative reinforcement bars

shall be at distance of one third of the clear span length

(between the supports)from face of the support (l/3).

Standard hooks

1:Hooks used for longitudinal tensile steel reinforcement bars shall be of 90 degree (right hook)

with an extension of at least 12 bar diameter at the free end of the bar and with a min.

diameter of bend of 6 bars diameter as shown in the figure below.

2:For all stirrups and tie bars 90 degree hooks shall be used with an

extension of at least 6 bar diameter at the free end of the bar and

with a min. Diameter of bend of 6 bar diameter shown in the figure below.

Structural Notes

Structural Notes

STANDARD BAR SPLICES

1:LAP SPLICES IN TENSION (USED IN ALL MEMBERS AND MUST IN COLUMNS)

 

  1. For nos. (#) 3, 4 & 5 bars splice length  = 12 inches.

Ii.   For no. 6 bars                                          splice length = 22 inches.

Iii. For no. 8 bars                                          splice length = 40 inches.

 

1:Compression splices (used in all members except columns)

1:For nos. (#) 3, 4 & 5 bars splice length = 12 inches.

2. For no. 6 bars                                          splice length = 15 inches.

3. For no. 8 bars                                          splice length = 20 inches.

  1. Spacer bars of min. 1.0″ diameter or concrete

Spacer of 1″ thickness shall be used between the reinforcement

Layers to allow the placement of concrete between the reinforcement bars.

 

  • Clear cover for slab = 0.75″
  • Clear cover for beam = 1.5″
  • Clear cover for column = 1.5″
  • Clear cover for foundation = 2.5″

GENERAL NOTES

  1. All the positive (bottom) reinforcement is shown as solid lines.
  2. All the negative (top) reinforcement shown as dashed (broken) line.
  3. All the positive (bottom) reinforcement shall be extended a minimum of 6″ into the supports (beams)
  4. All the negative (top) reinforcement shall be cut off at l/3 from face of the support (beam)

Where l is the clear length between the supports (beams).

  1. In the edge slab panels the negative (top) steel shall be extended downward into the beams in the

Form of hooks. Minimum hook length for #4 bars is 6″.

  1. Concrete used shall have a minimum 28 days cylinder crushing strength of 3000 psi.
  2. Steel used shall conform to astm specifications of a615 with a minimum yield strength of 40,000 psi.

From: http://civilglobal.com  Written By: Engr Sami Ullah Stanikzai